UPS Size Calculator

Estimate the UPS output watts and apparent power class you should look for, based on equipment load and headroom.

Advanced: power factor

Leave blank to use a 0.8 estimate. That is not a claim that every load has PF 0.8.

Result

Look for a UPS rated at least 750 W output and about 950 VA or higher based on the selected PF estimate.

Entered load
600 W
Headroom
25%
Minimum output watts
750 W
Estimated VA
~938 VA

Using PF 0.8 as an estimate

Check both the manufacturer watt rating and VA rating. A given VA class does not always have one matching watt rating.

How this was calculated

Limitations

  • This sizes output capacity, not battery runtime. Runtime depends on the UPS battery system and the manufacturer load curve.
  • Startup and inrush loads may need additional margin beyond the headroom you enter.
  • This is conservative sizing guidance, not electrical-safety or installation advice.